Installation Information

MINI-CSB INTERFACE TERMINALS

MINI-CSB

1

P5

8

BUILDING ALARM 3 BUILDING ALARM 3 RETURN BUILDING ALARM 4 BUILDING ALARM 4 RETURN BUILDING ALARM 5 BUILDING ALARM 5 RETURN BUILDING ALARM 6 BUILDING ALARM 6 RETURN

NOTE: 1. All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer-supplied.

2.The building alarms can be programmed to display the alarm functional name.

DESCRIPTION: INTERFACE WIRING INSTALLATION

NOTES AND TERMINAL LOCATIONS

 

DRAWING NO: 164201604---8

 

SHEET:

4 of 13

 

REVISION: A

DATE: 091505

 