Installation Information

Table I. UPS Cabinet Power Cable Terminations for the Powerware 9390---120/100,

9390---120/120, 9390---160/100, 9390---160/120, and 9390---160/160 (208V/220V Input and

208V/220V Output), and the Powerware 9390

---160/100, 9390---

160/120, and 9390

---160/160

(480V Input and 480V Output)

 

 

 

 

 

 

 

 

 

Terminal Function

Terminal

Function

Size of Pressure

 

Tightening

 

Type

 

Torque

 

Termination

 

 

Screw

 

 

 

 

Nm (lb in)

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier

E1

Phase A

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

and Bypass

 

 

 

 

 

 

 

 

 

 

E2

Phase B

2 ---

#2---

600 kcmill

 

56.5

(500)

 

1/2 in. Hex

(Single Input)

 

 

 

 

 

 

 

 

 

 

 

 

E3

Phase C

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier

E1

Phase A

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

(Dual Input)

 

 

 

 

 

 

 

 

 

 

E2

Phase B

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E3

Phase C

2 ---

#2---

600 kcmill

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

AC Input To Bypass

E6

Phase A

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

(Dual Input)

 

 

 

 

 

 

 

 

 

 

E7

Phase B

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E8

Phase C

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

Single-Feed to Dual-Feed

Rectifier

Phase A

 

 

N/A

 

12.5

(110)

 

M8 Hex Bolt

Transfer Wires from

 

 

 

 

 

 

 

 

 

 

Bypass

Phase A

 

 

N/A

 

12.5

(110)

 

M8 Hex Bolt

Rectifier Input Terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier

Phase B

 

 

N/A

 

12.5

(110)

 

M8 Hex Bolt

to Bypass Input Terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

Phase B

 

 

N/A

 

12.5

(110)

 

M8 Hex Bolt

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier

Phase C

 

 

N/A

 

12.5

(110)

 

M8 Hex Bolt

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

Phase C

 

 

N/A

 

12.5

(110)

 

M8 Hex Bolt

 

 

 

 

 

 

 

 

 

 

 

AC Output to

E9

Phase A

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

Critical Load

 

 

 

 

 

 

 

 

 

 

E10

Phase B

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E11

Phase C

2 ---

#2---

600 kcmill

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

DC Input from

E4

Positive

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

Battery to UPS

 

 

 

 

 

 

 

 

 

 

E5

Negative

2 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input and Output Neutral

E12

Neutral

8 ---

#2

---600 kcmil

 

56.5

(500)

 

1/2 in. Hex

Customer Ground

Ground

Ground

8

--- #14 1/0---

 

5.6

(50)

 

Slotted

NOTE: Customer ground can be run in any conduit listed in Table J.

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

DRAWING NO: 164201604---5

 

SHEET:

5 of 15

 

REVISION: A

DATE: 091505

 

A-16EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

Page 184
Image 184
Powerware 100160 kVA manual Drawing no