Product Specifications

15.2.2 UPS System Output

UPS Output Capacity

100% rated current

Output Voltage

¦1% (10% to 100% load)

Regulation

 

Output Voltage

208 Vac nominal, adjustable from 202 Vac to 214 Vac

Adjustment

220 Vac nominal, adjustable from 214 Vac to 226 Vac

(Nominal +/–3%)

480 Vac nominal, adjustable from 466 Vac to 494 Vac

Output Voltage Harmonic

1.5% max THD (linear load)

Content

5% max THD (nonlinear load)

Output Current

See Appendix A, Table E through Table G.

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

Output Voltage Phase

3° for 100% maximum load imbalance (linear load)

Displacement

 

Output Transients

5% for 100% load step or removal

Frequency Regulation

0.01 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting;

 

bypass within 0.5 Hz

Frequency Slew Rate

1 Hz per second maximum

Overload Capability

110% for 10 minutes

 

125% for 30 seconds

 

150% for 10 seconds

15.2.3 Environmental

Operating Temperature

0 to 40°C (32–104°F) without derating. The recommended

 

operating temperature is 25°C (77°F).

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

Storage Temperature

–25 to +60°C, excluding batteries (prolonged storage above

 

40°C causes rapid battery self-discharge)

Relative Humidity

5% to 95% maximum noncondensing

(operating and storage)

 

Acoustical Noise

65 dB at a 1m distance, c weighted

EMI Suppression

Meets FCC Regulation 47, Part 15, for class A devices

Electrostatic Discharge

Meets IEC 801-2 specifications. Withstands up to 25 kV pulse

(ESD) Immunity

without damage and with no disturbance or adverse effect to

 

the critical load.