Powerware 100160 kVA manual Power Wiring Installation Notes

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 180
Image 180

Installation Information

Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390---120/100 and 9390---160/100

 

 

Units

 

 

 

Basic Unit Rating at 0.9 lagging pF load

 

kVA

 

kW

 

 

 

 

 

Input and Bypass Input

 

VOLTS

Output

 

VOLTS

 

 

 

AC Input to UPS Rectifier (0.98 min. pF)

 

 

Full Load Current plus Battery Recharge Current

A

Amps

(3) Phases, (1) Ground

 

 

 

Minimum Conductor Size

 

 

 

AWG or kcmil

Number per Phase

 

(each)

 

 

 

AC Input to UPS Bypass

 

 

Full Load Current

B

Amps

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

Minimum Conductor Size

 

 

 

AWG or kcmil

Number per Phase

 

(each)

 

 

 

DC Input from Battery to UPS

 

Vdc

(1) Positive, (1) Negative

C

Amps@ (2.0V/cell)

Minimum Conductor Size

 

AWG or kcmil

Number per Pole

 

(each)

 

 

 

AC Output to Critical Load

 

 

Full Load Current

D

Amps

(3) Phases, (1) Neutral---if required, (1) Ground

 

Minimum Conductor Size

 

AWG or kcmil

Number per Phase

 

(each)

 

 

 

Neutral Bonding Jumper

---

AWG or kcmil

Minimum Conductor Size

(each)

Number (See Note 7)

 

 

Rating 50/60 Hz

100100

9090

208/220

480

208/220

480

 

 

300

130

3/0

 

4/0

(2)(1)

278/262

120

3/0

 

4/0

(2)(1)

384---480

432---480

252

252

2/0

 

2/0

(2)(2)

278/262

120

 

 

3/0

4/0

(2)(1)

1/0

2

(1)(1)

NOTE: Callout letters A, B, C, and D map to Drawing 164201604 ---4, sheets 1 of 6, 2 of 6, 4 of 6, 5 of 6, and 6 of 6.

Read and understand the following notes while planning and performing the installation:

1.Refer to national and local electrical codes for acceptable external wiring practices.

2.Material and labor for external wiring requirements are to be provided by designated personnel.

3.For external wiring, use 90° C copper wire. See the appropriate information in Table E through Table G. Wire sizes are based on using the specified breakers.

4.Wire ampacities are chosen from Table 310---16 of the NEC. Wire is 90°C specification.

5.If installing, as part of the UPS system, a maintenance bypass without a rectifier input breaker, a minimum of two separate feeds with upstream feeder breakers, or one feed with two upstream feeder breakers, must be provided: one for the UPS and one for the maintenance bypass input. DO NOT use one feed or a single-feeder breaker to supply both the UPS and the maintenance bypass.

 

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO:

164201604---5

 

SHEET: 1 of 15

 

REVISION:

B

DATE: 032406

A-12EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

Page 180
Image 180
Powerware 100160 kVA manual Power Wiring Installation Notes