Installation Information

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table O. INPUT/OUTPUT Ratings for Powerware 9390---120/100 and 9390---160/100 Parallel Systems

 

 

 

 

 

Configuration

 

 

 

Units

 

Rating 50/60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic Unit Rating at 0.9 lagging pF load

 

kVA

 

100

 

 

100

 

 

 

 

 

 

 

kW

 

90

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input and Bypass Input

 

 

VOLTS

 

208/220

 

480

 

 

 

 

 

 

Output

 

 

VOLTS

 

208/220

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input from UPM

 

 

Amps

 

278/262

 

120

 

 

 

 

 

 

Full Load Current for each Module

 

D

 

 

 

 

 

 

 

All

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size for each Module

 

AWG or kcmil

 

See Table

E through

 

 

 

 

 

 

Number per Phase for each Module

 

 

(each)

 

Table G for wire size.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

 

278/262

 

120

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1+1

AC Output to Critical Load

 

G

Amps

 

278/262

 

120

 

 

 

 

 

Full Load Current

 

 

 

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

---

AWG or kcmil

 

1/0

 

 

4

 

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

(1)

 

 

(1)

 

 

 

 

 

 

Number (See Note 27)

 

 

(each)

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

 

556/524

 

240

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

2+0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

 

G

 

 

 

 

 

 

 

 

 

 

 

 

and

Full Load Current

 

Amps

 

556/524

 

240

 

 

 

 

 

2+1

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

---

AWG or kcmil

 

3/0

 

 

1/0

 

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

(1)

 

 

(1)

 

 

 

 

 

 

Number (See Note 27)

 

 

(each)

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

 

834/786

 

360

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

3+0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

 

G

 

 

 

 

 

 

 

 

 

 

 

 

and

Full Load Current

 

Amps

 

834/786

 

360

 

 

 

 

 

3+1

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

---

AWG or kcmil

 

1/0

 

 

2/0

 

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

(1)

 

 

 

 

 

 

Number (See Note 27)

 

 

(each)

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

 

1112/1048

 

480

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4+0

AC Output to Critical Load

 

G

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

 

1112/1048

 

480

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

---

AWG or kcmil

 

2/0

 

 

2/0

 

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

(1)

 

 

 

 

 

 

Number (See Note 27)

 

 

(each)

 

 

 

 

 

 

 

 

 

 

NOTE: Callout letters D, F, and G map to Drawing 164201604 ---4, sheets 4 of 6, 5 of 6,

 

 

 

 

 

 

and 6 of 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201604---5

 

 

 

SHEET:

12 of 15

 

 

 

 

 

 

 

REVISION: B

 

 

 

DATE: 032406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

A-23

Page 191
Image 191
Powerware 100160 kVA manual Configuration Units Rating 50/60 Hz