Installing the UPS System
Parallel System Installation Checklist
-Each cabinet in the parallel system is placed in its installed location.
-All conduits and cables are properly routed to the UPMs and to the parallel tie or distribution cabinet.
-All power cables are properly sized and terminated.
-The bypass source feeding the optional bypass of the parallel tie cabinet and the UPMs is from the same source of supply and is a
-Neutral conductors are installed or bonded to ground as per requirements.
-A ground conductor is properly installed.
-Computer Area Network (CAN) wiring between the UPMs is properly installed.
-Pull chain wiring between the UPMs is properly installed.
-Adequate workspace exists around the UPMs, parallel tie cabinet, and other cabinets.
-Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.