Installation Information

AC INPUT

To UPS

Input

MBP

MIB

Output from

UPS

MAINTENANCE

BYPASS PANEL

(PROVIDED BY OTHERS)

K5

STATIC

Backfeed SWITCH

K3

UPS

BATTERY

BREAKER

BATTERY CABINET

MIB:

MAINTENANCE ISOLATION BREAKER

CRITICAL LOAD DISTRIBUTION UNIT

MBP: MAINTENANCE BYPASS BREAKER

TYPICAL MAINTENANCE BYPASS PANEL POWER FLOW

NOTE: If installing, as part of the UPS system, a maintenance bypass without a rectifier input breaker, a minimum of two separate feeds with upstream feeder breakers, or one feed with two upstream feeder breakers, must be provided: one for the UPS and one for the maintenance bypass input. DO NOT use one feed or a single-feeder breaker to supply both the UPS and the maintenance bypass.

 

 

 

 

DESCRIPTION:

UPS SYSTEM ONELINE DRAWING

 

 

 

 

 

DRAWING NO:

164201604---4

SHEET: 3 of 6

 

 

 

 

 

REVISION:

A

DATE: 091505

 

 

 

 

 

 

 

 

 

A-8

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S

164201604 Rev B powerware.com

Page 176
Image 176
Powerware 100160 kVA manual Typical Maintenance Bypass Panel Power Flow