Installing the UPS System
6.When all wiring is complete, reinstall the safety shield panels removed in previous steps. Secure with the retained hardware.
7.Close the control panel door and secure with the retained hardware.
8.Reinstall the doors removed previously and secure with the retained hardware.
9.Close the doors and secure the latch.
10.Refer to the manual supplied with the
3.2.8 Installing Accessories and Parallel System Control Wiring
To install an optional Remote Emergency
3.3 Initial Startup
Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms specified on page
3.4 Completing the Installation Checklist
The final step in installing the UPS system is completing the following Installation Checklist. This checklist ensures that you have completely installed all hardware, cables, and other equipment. Complete all items listed on the checklist to ensure a smooth installation. Make a copy of the Installation Checklist before filling it out, and retain the original. If installing a parallel system, complete the Parallel System Installation Checklist in addition to the Installation Checklist.
After the installation is complete, your Eaton service representative must verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters. Service personnel may request a copy of the completed Installation Checklist to verify all applicable equipment installations have been completed.
NOTE The Installation Checklist MUST be completed prior to starting the UPS system for the first time.