Installation Information

CAN

UPM

1

UPM

2

UPM

3

(IF INSTALLED)

PULL CHAIN

UPM

4

(IF INSTALLED)

NOTE: This drawing is for parallel wiring purposes and is not a floor layout plan. UPMs can be placed in any physical order.

PARALLEL SYSTEM CAN AND BACKUP CONTROL (PULL CHAIN)

CAN Wiring Terminations

From UPM 1 CAN Card

To UPM 2 CAN Card

To UPM 3 CAN Card

(If Installed)

 

 

J3–8 (L)

J3–8 (L)

J3–8 (L)

J3–9 (H)

J3–9 (H)

J3–9 (H)

J3–10 (Shield)

J3–10 (Shield)

J3–10 (Shield)

To UPM 4 CAN Card

(If Installed)

J3–8 (L)

J3–9 (H)

J3–10 (Shield)

TWISTED PAIR

TWISTED PAIR

TWISTED PAIR

UPM 1

UPM 2

UPM 3

UPM 4

CAN CARD J3

CAN CARD J3

CAN CARD J3

CAN CARD J3

 

 

(IF INSTALLED)

(IF INSTALLED)

PARALLEL SYSTEM CAN WIRING

DESCRIPTION: INTERFACE WIRING INSTALLATION

NOTES AND TERMINAL LOCATIONS

 

DRAWING NO: 164201604---8

 

SHEET:

10 of 13

 

REVISION: A

DATE: 091505

 