Powerware 100160 kVA manual RMP, RIM, or SCM Wiring Terminations

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 213
Image 213

Installation Information

19.Conduit must be installed between the UPS cabinet and the RMP II, RIM II, or SCM II for signal wiring. Conduit must be installed between the device and the power source for power wiring. Install the signal wiring in separate conduit from the power wiring.

20.Conduit and wiring between the UPS and the RMP II, RIM II, or SCM II is to be supplied by the customer.

21.Maximum distance between the UPS cabinet and RMP II, RIM II, or SCM II is not to exceed 500 feet.

22.Use Class 1 wiring methods (as defined by the NEC) for RMP II, RIM II, or SCM II power and signal wiring. Power wiring should be a minimum of 22 AWG and a maximum of 14 AWG. The wire should be rated for 1A minimum.

23.RMP II, RIM II, or SCM II signal wiring should be a minimum of 22 AWG and a maximum of 14 AWG. The wire should be twisted pair, rated for 5A maximum.

24.Use only 75°C copper wire.

25.120 Vac for the RMP II, RIM II, or SCM II should be provided from the critical bus by facility planners or the customer.

26.See Table X and Chapter 6 for CAN Bridge Card and RMP II, RIM II, or SCM II installation.

RMP, RIM, or SCM Wiring Terminations

From UPS CAN Card

To RMP, RIM, or SCM

Tightening Torque

Remarks

Nm (lb in)

 

 

 

 

 

J3–6

 

 

TB1–5 (RDX*)

0.9 (8)

 

(TX)

Use Twisted Pair

J3–7 (TX)

TB1–4 (RDX)

0.9 (8)

 

N/A

TB3 Line

0.9 (8)

 

N/A

TB3 Neutral

0.9 (8)

 

N/A

Ground Terminal

2.7 (24) Maximum

 

GROUND

TERMINAL

NEUTRAL

120 VAC

 

FROM

LINE

CRITICAL

 

BUS

UPS CAN

CARD J3

RMP II, RIM II, OR SCM II

TWISTED PAIR

DESCRIPTION: INTERFACE WIRING INSTALLATION

NOTES AND TERMINAL LOCATIONS

DRAWING NO: 164201604---8

 

SHEET:

13 of 13

REVISION: A

DATE: 091505

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

A-45

Page 213
Image 213
Powerware 100160 kVA manual RMP, RIM, or SCM Wiring Terminations