Powerware 100160 kVA manual Table J. Power Cable Conduit Requirements Cont’d

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 186
Image 186

Installation Information

Table J. Power Cable Conduit Requirements (Cont’d)

UPS Model

Voltage

Terminal

Number of

Minimum Conduit

Number of

Wires in

Trade Size (inches)

Conduits

 

 

 

Conduit

 

 

 

 

 

 

 

AC Input to UPS

4

3-1/2

2

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

208/220

AC Input to Bypass

5

3-1/2

2

Powerware

AC

(A, B, C, Neut, Gnd)

 

 

 

9390---160/160

 

Output

5

3-1/2

2

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

2-1/2

1

 

DC

(Positive), (Negative), Gnd

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

2

2

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

480

AC Input to Bypass

5

2

2

Powerware

AC

(A, B, C, Neut, Gnd)

 

 

 

9390---160/160

 

Output

5

2

2

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

2-1/2

1

 

DC

(Positive), (Negative), Gnd

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

DRAWING NO: 164201604---5

 

 

SHEET: 7 of 15

 

REVISION:

A

DATE:

091505

 

 

 

A-18EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com