Installation Information

Table J. Power Cable Conduit Requirements (Cont’d)

UPS Model

Voltage

Terminal

Number of

Minimum Conduit

Number of

Wires in

Trade Size (inches)

Conduits

 

 

 

Conduit

 

 

 

 

 

 

 

AC Input to UPS

4

3-1/2

2

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

208/220

AC Input to Bypass

5

3-1/2

2

Powerware

AC

(A, B, C, Neut, Gnd)

 

 

 

9390---160/160

 

Output

5

3-1/2

2

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

2-1/2

1

 

DC

(Positive), (Negative), Gnd

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

2

2

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

480

AC Input to Bypass

5

2

2

Powerware

AC

(A, B, C, Neut, Gnd)

 

 

 

9390---160/160

 

Output

5

2

2

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

2-1/2

1

 

DC

(Positive), (Negative), Gnd

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

DRAWING NO: 164201604---5

 

 

SHEET: 7 of 15

 

REVISION:

A

DATE:

091505

 

 

 

A-18EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

Page 186
Image 186
Powerware 100160 kVA manual Table J. Power Cable Conduit Requirements Cont’d