Chapter 3

Installing the UPS System

3.1 Preliminary Installation Information

W A R N I N G

Installation should be performed only by qualified personnel.

Refer to the following while installing the UPS system:

￿Appendix A contains installation drawings and additional installation notes.

￿Dimensions are in millimeters and inches.

￿Do not tilt the cabinets more than 10° during installation.

￿The conduit landing plates are to be removed to add conduit landing holes as required. Plate material is 16 gauge steel (1.5 mm/0.06″ thick).

￿The cabinets must be installed on a level floor suitable for computer or electronic equipment.

￿If perforated floor tiles are required for ventilation, place them in front of the UPS. See Table A on page A-3 for equipment weight and point loading.

￿Details about control wiring are provided in each procedure for connecting options and features. Drawing 164201604-8 and Table R through Table X starting on page A-33 identify the control wiring terminations.

3.2UPS Cabinet Installation

To install a UPS cabinet, perform the procedures in the following paragraphs.

NOTE When a line-up-and-match UPS system is ordered together with battery cabinets, the first battery cabinet is supplied with two cosmetic covers. The UPS cabinet, additional battery cabinets, and other ancillary cabinets are supplied without cosmetic covers.

NOTE When a UPS system is ordered together with battery cabinets for standalone installation, the first battery cabinet is supplied with two cosmetic covers. Additional battery cabinets are supplied without cosmetic covers. Cosmetic covers must be ordered for the UPS cabinet and/or other ancillary cabinets.

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

3-1

Page 23
Image 23
Powerware 100160 kVA manual Installing the UPS System, Preliminary Installation Information, UPS Cabinet Installation