Powerware 100160 kVA manual Table M. Maximum DC Input Circuit Breaker Ratings

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 188
Image 188

Installation Information

19.There is no DC disconnect device within the UPS.

20.A battery disconnect switch is recommended, and may be required by NEC or local codes when batteries are remotely located. The battery disconnect switch should be installed between the battery and the UPS.

21.External DC input overcurrent protection and disconnect switch for the remote battery location is to be provided by the user. Table M lists the maximum rating for continuous-duty rated circuit breakers satisfying the criteria for both.

Table M. Maximum DC Input Circuit Breaker Ratings

UPS Model

Input Voltage Rating

208V/220V

480V

 

Powerware 9390---120/100

400A

400A

Powerware 9390---160/100

 

 

Powerware 9390---120/120

450A

450A

Powerware 9390---160/120

 

 

Powerware 9390---160/160

600A

600A

22.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 2 volts per cell.

23.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current.

24.If the conductors used for DC input from the battery cabinets to the UPS are those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the same supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

DRAWING NO: 164201604---5

 

SHEET: 9 of 15

 

REVISION: A

DATE: 091505

A-20EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

Page 188
Image 188
Powerware 100160 kVA manual Table M. Maximum DC Input Circuit Breaker Ratings