Installing the UPS System
12.Remove the screws securing the bottom and right side internal safety shield panels and remove the panels to gain access to the bottom conduit landing plate.
NOTE When installing UV trip and Aux battery interface wiring to the UPS interface terminals, conduit must be installed between the UPS and battery cabinets.
13.Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit holes (see Drawing
14.Reinstall the conduit landing plate and install the conduit.
15.Route the UV trip and Aux wiring from the battery cabinet to the UPS.
16.Connect the wiring to the TB2 terminals.
17.If wiring
18.When all wiring is complete, reinstall the safety shield panels removed in previous steps. Secure with the retained hardware.
19.Close the control panel door and secure with the retained hardware.
20.Reinstall the doors removed previously and secure with the retained hardware.
21.Close the doors and secure the latch.
3.2.7.3 X-Slot Connections
NOTE LAN and telephone drops for use with
NOTE When installing external wiring to
For installation and setup of an
1.If not already installed, install the LAN and telephone drops.
2.Unfasten the front door latch and swing the door open.
3.Remove the UPS cabinet
4.Reinstall the conduit landing plate and install the conduit.
5.Route and install the LAN, telephone, and other cables to the appropriate
EATON Powerware® 9390 UPS |