Powerware 100160 kVA manual Single UPM Shutdown, Restarting a Single UPM

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 135
Image 135

UPS Operating Instructions

10.2.5 Single UPM Shutdown

To shut down a single UPM, perform the following procedure:

NOTE The UPM can be shut down only if remaining UPMs can support the critical load without being overloaded.

1.Press the CONTROLS pushbutton on the main menu bar on the UPM to be shut down. The System Controls screen appears.

2.Press the pushbutton to display System Controls Screen 2.

3.Press the PM OFF pushbutton on the System Controls menu bar.

The power module (PM) status indicates SHUTDOWN. The input and output contactors open, the battery breaker or disconnect is tripped, and the power module is turned off.

4.Open the input and bypass (if dual feed) feeder circuit breakers supplying the shutdown UPM.

NOTE The monitor screen continues to be active until the UPM is isolated from the critical bus.

W A R N I N G

Power is present inside the shutdown UPM cabinet due to connection to the critical bus, until the UPM output breaker is opened.

5.If it is necessary to isolate the UPM from the critical bus, open the module output breaker on the tie cabinet or distribution panel.

10.2.6Restarting a Single UPM

To restart a single UPM, perform the following procedure:

1.If the UPM was isolated from the critical bus, close the module output breaker on the tie cabinet or distribution panel.

2.Observe the UPM control panel display becoming active, indicating logic power. UPM logic is being powered from the critical bus.

3.Close the UPM input feeder circuit breaker.

4.If the UPM is dual feed, close the UPM Bypass input feeder circuit breaker.

5.Press the CONTROLS pushbutton on the main menu bar of the UPM. The System Controls screen appears.

6.On the System Controls screen, the power module (PM) status should indicate

SHUTDOWN.

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

10-11

Page 135
Image 135
Powerware 100160 kVA manual Single UPM Shutdown, Restarting a Single UPM