Installation Information

16.Conduit must be installed between the UPM cabinets for parallel interface wiring. Install the interface wiring in separate conduit from the power wiring.

17.Use Class 1 wiring methods (as defined by the NEC) for parallel interface wiring. The wire should be shielded twisted pair, rated for 5 amps maximum.

18.See Table X and Chapter 6 for Powerware Hot Sync CAN Bridge Card interface wiring.

Table X. Powerware Hot Sync CAN Bridge Card Interface Connections

Terminal J3

 

 

Name

Description

1

 

Alarm

Programmable UPS alarm. Activated by a remote

2

 

Alarm Rtn

dry contact closure.

3

 

Alarm Relay NC

Normally-closed contact opens when UPS is on

 

bypass.

 

 

 

 

4

 

Alarm Relay Com

Bypass contact return.

5

 

Alarm Relay NO

Normally-open contact closes when UPS is on

 

bypass.

 

 

 

 

 

 

 

 

 

6

 

TX

Remote Monitor Panel II (RMP II), Relay Interface

 

 

 

 

Module II (RIM II), and Supervisory Contact

7

 

 

 

 

 

 

Module II (SCM II) connections.

TX

8

 

CAN L

Computer Area Network (CAN) Input for parallel

9

 

CAN H

 

operation.

10

 

Shield

 

 

 

 

 

J3

 

CONNECTIONS FOR PARALLEL SYSTEM CONTROL

CONNECTIONS FOR RMP II, RIM II, OR SCM II

CONNECTIONS FOR BYPASS STATUS

BUILDING ALARM 2 REPLACEMENT

POWERWARE HOT SYNC CAN BRIDGE CARD

NOTE: All interface wiring is to be provided by the customer.

DESCRIPTION: INTERFACE WIRING INSTALLATION

NOTES AND TERMINAL LOCATIONS

DRAWING NO: 164201604---8

 

SHEET:

9 of 13

REVISION: A

DATE: 091505

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

A-41

Page 209
Image 209
Powerware 100160 kVA manual Powerware HOT Sync can Bridge Card