Installing the UPS System
3.2.1 Unloading the Powerware 9390 UPS Cabinet from the Pallet
The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet, perform the following procedure:
W A R N I N G
The UPS cabinet is heavy. See Table A on page
C A U T I O N
Do not tilt cabinets more than 10° from vertical.
1.If not already accomplished, use a forklift or pallet jack to move the cabinet to the installation area, or as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the skids on the bottom of the unit.
NOTE Verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table A on page
2.Unfasten the front door latch and swing the door open (see Figure
3.Remove the doors. Remove the retaining screws located inside each door at the top and bottom hinge pivot points, then lift the door off. Retain the hardware for later use.
4.If the leveling feet are not fully retracted, turn the leveling feet until they are retracted.
5.Remove the four bolts securing the front shipping bracket to the cabinet and four bolts securing the bracket to the pallet (see Figure
6.Remove the four bolts securing the rear shipping bracket to the pallet. Do NOT remove the four bolts securing the bracket to the cabinet (see Figure
7.Remove the four bolts securing the removable skid and remove the skid (see Figure
EATON Powerware® 9390 UPS |