Installation Information

9.The UPS DC UVR trip and Battery Aux signal wiring from the UPS must be connected to the DC source disconnect device.

10.Battery Aux and UVR wiring should be a minimum of 18 AWG.

Table S. Battery Disconnect Interface

BATTERY

BREAKER OR

DISCONNECT

 

UPS

 

 

TB1

 

BATTERY AUX +

5

 

BATTERY AUX ---

6

 

BATTERY UVR +

7

 

BATTERY UVR ---

8

 

 

 

Table T. Alarm Relay Contact

 

 

ALARM RELAY

TB2

 

 

5

 

 

5

UPS

 

 

 

7

 

 

8

 

CONTACT RATING

 

 

Switched Voltage:

277Vac 28 Vdc

Maximum Current: 5A

Minimum Wire Size: 22 AWG

NOTE: Relays are shown in de-energized state. Relays change state when the

UPS is in Normal mode.

 

 

DESCRIPTION: INTERFACE WIRING INSTALLATION

 

 

 

 

 

 

NOTES AND TERMINAL LOCATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201604---8

 

 

SHEET: 5 of 13

 

 

 

 

 

REVISION: B

 

DATE:

032406

 

 

 

 

 

 

 

 

 

 

 

 

 

 