UPS Installation Plan and Unpacking
2.2.1 Environmental Considerations
The life of the UPS system is adversely affected if the installation does not meet the following guidelines:
The system must be installed on a level floor suitable for computer or electronic equipment.
The system must be installed in a temperature and humidity controlled indoor area free of conductive contaminants.
Failure to follow guidelines may void your warranty.
2.2.2 Preparing for Wiring the UPS System
NOTE If installing, as part of the UPS system, a maintenance bypass without a rectifier input breaker, a minimum of two separate feeds with upstream feeder breakers, or one feed with two upstream feeder breakers, must be provided: one for the UPS and one for the maintenance bypass input. DO NOT use one feed or a single feeder breaker to supply both the UPS and the maintenance bypass.
For external wiring requirements, including the minimum AWG size of external wiring, see Table E through Table G starting on page