Powerware 100160 kVA manual K3 AUX Contact Rating

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 208
Image 208

Installation Information

15.120 Vac should be provided from the critical bus by facility planners or the customer. See Table W.

Table W. Typical Maintenance Bypass Panel Key Switch Control Wiring

MAINTENANCE BYPASS PANEL

(PROVIDED BY OTHERS)

Solenoid

Neutral

Key

Switch

Lamp

NOTE: THE RED OK TO GO TO MAINTENANCE BYPASS ILLUMINATES ONLY WHEN THE UPS MODULE IS NOT ONLINE (K3 OUTPUT CONTACTOR IS OPEN).

120VAC

Fused

TB2 9

10

Output

Contactor

K3

UPS

K3 AUX CONTACT RATING

Switched Voltage:

120 Vac at 6A Maximum

 

240 Vac at 4A Maximum

 

24 Vdc at 6A Maximum

Minimum Wire Size: 22 AWG

DESCRIPTION: INTERFACE WIRING INSTALLATION

NOTES AND TERMINAL LOCATIONS

 

DRAWING NO: 164201604---8

 

SHEET:

8 of 13

 

REVISION: A

DATE: 091505

 

A-40EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com