Installation Information

Table F. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390---120/120 and 9390---160/120

 

 

Units

 

 

 

Basic Unit Rating at 0.9 lagging pF load

 

kVA

 

kW

 

 

 

 

 

Input and Bypass Input

 

VOLTS

Output

 

VOLTS

AC Input to UPS Rectifier (0.98 min. pF)

 

 

Full Load Current plus Battery Recharge Current

A

Amps

(3) Phases, (1) Ground

 

Minimum Conductor Size

 

AWG or kcmil

Number per Phase

 

(each)

 

 

 

AC Input to UPS Bypass

 

 

Full Load Current

B

Amps

(3) Phases, (1) Neutral---if required, (1) Ground

 

Minimum Conductor Size

 

AWG or kcmil

Number per Phase

 

(each)

 

 

 

DC Input from Battery to UPS

 

Vdc

(1) Positive, (1) Negative

C

Amps@ (2.0V/cell)

Minimum Conductor Size

 

AWG or kcmil

Number per Pole

 

(each)

 

 

 

AC Output to Critical Load

 

 

Full Load Current

D

Amps

(3) Phases, (1) Neutral---if required, (1) Ground

 

Minimum Conductor Size

 

AWG or kcmil

Number per Phase

 

(each)

 

 

 

Neutral Bonding Jumper

---

AWG or kcmil

Minimum Conductor Size

(each)

Number (See Note 7)

 

 

Rating 50/60 Hz

120120

108108

208/220

480

208/220

480

 

 

360

160

4/0

 

4/0

(2)(1)

333/315

144

4/0

 

4/0

(2)(1)

384---480

432---480

302

302

3/0

 

3/0

(2)(2)

333/315

144

 

 

4/0

4/0

(2)(1)

1/0

2

(1)(1)

NOTE: Callout letters A, B, C, and D map to Drawing 164201604 ---4, sheets 1 of 6, 2 of 6, 4 of 6, 5 of 6, and 6 of 6.

6.The bypass feed into this equipment uses three or four wires. The rectifier feed into this equipment uses three wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment operation.

7.If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper. See Table E through Table G for neutral bonding jumper wire sizes. Bonding jumper must be copper wire.

C A U T I O N

HIGH IMPEDANCE GROUND SOURCES - If the source of supply is a high impedance ground (IT) type, the input neutral conductor must be connected from the source of supply. If there is no output neutral connected to the UPS, the neutral-forming tranformer kit (PN 103005400) may be used instead of pulling a neutral from the source. If the load requires a neutral then an input neutral conductor must be pulled into the UPS. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS.

 

 

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201604---5

 

SHEET:

2 of 15

 

 

 

 

 

 

 

 

 

 

 

 

 

REVISION:

B

 

DATE: 032406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

A-13

Page 181
Image 181
Powerware 100160 kVA manual Power Wiring Installation Notes