Using Features and Options
11.4 Relay Interface Module II
An optional RIM II uses relay contact closures to indicate the operating status and alarm condition of the UPS system. The RIM II can be
Figure 11-2. Relay Interface Module II
The RIM II can provide the status and alarm signals shown in Table
Table 11-2. Customer Interface Connectors
Status | J1 through J4 | Description |
|
|
|
UPS AVAILABLE | Pins 1 and 12 | Contacts are closed when the UPS is operating in |
|
| Normal mode or ready to supply the load. |
|
|
|
UPS OFFLINE | Pins 3 and 13 | Contacts are open when the UPS is offline. |
|
| Contacts are closed when the UPS is operating in |
|
| Normal mode. |
|
|
|
BATTERY WEAK | Pins 5 and 14 | Contacts are closed when approximately two minutes of |
|
| battery time is remaining, before the critical load is lost. |
|
|
|
UTILITY FAILURE | Pins 6 and 15 | Contacts are closed when Utility Failure is detected. |
|
|
|