UPS Operating Instructions

3.The UPS is now operating in Bypass mode and the BYPASS status indicator is illuminated.

The power module (PM) status indicates READY. The system is now on bypass and the UPS power processor remains on.

W A R N I N G

Power is present inside the UPS cabinets.

10.1.5 Transfer from Bypass to Normal Mode

To transfer the critical load to Normal mode, perform the following procedure:

1.Press the CONTROLS pushbutton on the main menu bar. The System Controls screen appears.

2.Press the NORMAL pushbutton on the System Controls menu bar.

The UPS transfers to Normal mode. If the power processor is not available, the system remains on bypass and an alarm sounds.

3.The UPS is now operating in Normal mode, and the NORMAL status indicator is illuminated.

The power module (PM) status indicates ONLINE.

10.1.6Transfer from Normal to Bypass Mode and Shut Down UPS

To transfer the critical load to Bypass mode and shut down the UPS, perform the following procedure:

1.Transfer the critical load to bypass by performing the procedure in paragraph 10.1.4.

2.Press the CONTROLS pushbutton on the main menu bar. The System Control screen appears.

3.Press the pushbutton to display System Controls Screen 2.

4.Press the PM OFF pushbutton on the System Controls menu bar.

The power module (PM) status indicates SHUTDOWN. The input and output contactors open, the battery breaker or disconnect is tripped, and the power module is turned off. The bypass source supplies the critical load.

W A R N I N G

Power is present inside the UPS cabinets.

10-4EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

Page 128
Image 128
Powerware 100160 kVA manual Transfer from Bypass to Normal Mode, Transfer from Normal to Bypass Mode and Shut Down UPS