Installation Information
1.The UPS equipment operating environment must meet the weight requirements shown in Table A and the size requirements shown on Drawing
2.The UPS cabinet is palleted separately for shipping.
3.Do not tilt cabinets more than 10˚ during handling.
4.Dimensions are in millimeters (inches).
5.The cabinet can be installed in
Table A. UPS Cabinet Weight
| Voltage |
| Weight |
| ||
Model |
| kg (lb) |
| |||
|
|
|
| |||
|
|
|
|
| ||
| Input | Output | Shipping | Installed | Point Loading | |
|
|
|
|
|
| |
Powerware | 208V/220V | 208V/220V | 531 (1170) | 504 (1110) | 6 at 84 (185) | |
|
|
|
|
| ||
480V | 480V | 467 (1030) | 440 (970) | 6 at 73 (162) | ||
| ||||||
|
|
|
|
|
| |
Powerware | 208V/220V | 208V/220V | 531 (1170) | 553 (1110) | 6 at 84 (185) | |
|
|
|
|
| ||
480V | 480V | 467 (1030) | 440 (970) | 6 at 73 (162) | ||
| ||||||
|
|
|
|
|
| |
Powerware | 208V/220V | 208V/220V | 581 (1280) | 553 (1220) | 6 at 92 (204) | |
|
| |||||
480V | 480V | |||||
|
|
|
| |||
|
|
|
|
|
| |
Powerware | 208V/220V | 208V/220V | 581 (1280) | 553 (1220) | 6 at 92 (204) | |
|
| |||||
480V | 480V | |||||
|
|
|
| |||
|
|
|
|
|
| |
Powerware | 208V/220V | 208V/220V | 581 (1280) | 553 (1220) | 6 at 92 (204) | |
|
| |||||
480V | 480V | |||||
|
|
|
|
6.The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet | Minimum clearance over the UPS cabinet is |
| 457.2 mm (18 in.) for ventilation |
|
|
From Front of Cabinet | 914.4 mm (36 inches) working space |
|
|
From Back of Cabinet | None required |
|
|
From Right Side of Cabinet | None required |
|
|
From Left Side of Cabinet | None required |
|
| DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS |
|
|
| ||||
|
| DRAWING NO: |
|
| SHEET: 1 of 2 |
|
|
| |
|
| REVISION: | A | DATE: | 091505 |
|
|
| |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| EATON Powerware® 9390 UPS |