Installation Information

14.External overcurrent protection is not provided by this product, but is required by codes. Refer to Table E through Table G for wiring requirements. If an output lockable disconnect is required, it is to be supplied by the user.

15.Table K lists the maximum rating for input circuit breakers. When wiring a single-feed input, the rating requirements for the input circuit breakers are superceded by the ratings listed in Table L.

Table K. Maximum Input Circuit Breaker Ratings

UPS Model

 

Input Voltage Rating

 

 

 

 

 

 

 

 

208V/220V

 

480V

 

 

 

 

Powerware 9390---120/100

80% Rated

 

450A

 

200A

Powerware 9390---160/100

100% Rated

 

350A

 

150A

Powerware 9390---120/120

80% Rated

 

500A

 

225A

Powerware 9390---160/120

100% Rated

 

450A

 

175A

Powerware 9390---160/160

80% Rated

 

700A

 

300A

100% Rated

 

600A

 

250A

 

 

 

C A U T I O N

To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table K in accordance with the National Electrical code, ANSI/NFPA 70.

16.Source protection for the AC input to bypass should be treated as if supplying a 160 kVA three-phase transformer, to allow for inrush current if an IDC with a transformer is installed. Bypass input wiring and bypass input breaker rating should be treated as if supplying a 160 kVA load, regardless of the rating of the UPS.

17.The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values for AC output to critical load shown in Table E through Table G. The recommended line-to-line load unbalance is 50% or less.

18.Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by the user. Table L lists the maximum rating for bypass and output circuit breakers satisfying the criteria for both.

 

 

Table L. Maximum Bypass and Output Circuit Breaker Ratings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Model

 

Output Voltage Rating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208V/220V

 

480V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware 9390---120/100

 

80% Rated

 

450A

 

200A

 

 

 

 

 

 

Powerware 9390---160/100

 

100% Rated

 

350A

 

150A

 

 

 

 

 

 

Powerware 9390---120/120

 

80% Rated

 

500A

 

225A

 

 

 

 

 

 

Powerware 9390---160/120

 

100% Rated

 

450A

 

175A

 

 

 

 

 

 

Powerware 9390---160/160

 

80% Rated

 

700A

 

300A

 

 

 

 

 

 

 

100% Rated

 

600A

 

250A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO: 164201604---5

 

SHEET: 8 of 15

 

 

 

 

 

 

REVISION: A

 

DATE:

091505

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual

S 164201604 Rev B powerware.com

A-19

Page 187
Image 187
Powerware 100160 kVA manual Table L. Maximum Bypass and Output Circuit Breaker Ratings