UPS Operating Instructions

10.2.3 Transfer Parallel System from Normal to Bypass Mode

To transfer the critical load to Bypass mode, perform the following procedure:

C A U T I O N

In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.

1.Press the CONTROLS pushbutton on the main menu bar on any UPM. The System Controls screen appears.

2.Press the BYPASS pushbutton on the System Controls menu bar of any UPM.

The UPMs transfer to Bypass mode and the critical load is immediately supplied by the bypass source. If the bypass source is not available, the power processor remains on and an alarm sounds.

3.The UPMs are now operating in Bypass mode and the BYPASS status indicator on each UPM is illuminated.

The power module (PM) status indicates READY on each UPM. The system is now on bypass and the UPM power processors remain on.

W A R N I N G

Power is present inside the UPM cabinets.

10.2.4 Transfer Parallel System from Bypass to Normal Mode

To transfer the critical load to Normal mode, perform the following procedure:

1.Press the CONTROLS pushbutton on the main menu bar on any UPM. The System Control screen appears.

2.Press the NORMAL pushbutton on the System Controls menu bar of any UPM.

The UPMs transfer to Normal mode. If the power processor is not available, the system remains on bypass and an alarm sounds.

3.The UPMs are now operating in Normal mode, and the NORMAL status indicator on each UPM is illuminated.

The power module (PM) status indicates ONLINE on each UPM.

10-10EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com