Installation Information

Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390---160/160

 

 

 

Units

Rating 50/60 Hz

 

 

 

 

 

 

Basic Unit Rating at 0.9 lagging pF load

 

 

kVA

160

160

 

 

kW

144

144

 

 

 

 

 

 

 

 

 

Input and Bypass Input

 

 

VOLTS

208/220

480

Output

 

 

VOLTS

208/220

480

 

 

 

 

 

 

AC Input to UPS Rectifier (0.98 min. pF)

 

 

 

 

 

Full Load Current plus Battery Recharge Current

A

 

Amps

480

210

(3) Phases, (1) Ground

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

AWG or kcmil

400

1/0

Number per Phase

 

 

(each)

(2)

(2)

 

 

 

 

 

 

AC Input to UPS Bypass

 

 

 

 

 

Full Load Current

B

 

Amps

444/420

192

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

Minimum Conductor Size

 

 

AWG or kcmil

400

1/0

Number per Phase

 

 

(each)

(2)

(2)

 

 

 

 

 

 

DC Input from Battery to UPS

 

 

Vdc

384---480

432---480

(1) Positive, (1) Negative

C

 

Amps@ (2.0V/cell)

403

403

Minimum Conductor Size

 

 

AWG or kcmil

250

250

Number per Pole

 

 

(each)

(2)

(2)

 

 

 

 

 

 

AC Output to Critical Load

 

 

 

 

 

Full Load Current

D

 

Amps

444/420

192

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

Minimum Conductor Size

 

 

AWG or kcmil

400

1/0

Number per Phase

 

 

(each)

(2)

(2)

 

 

 

 

 

 

Neutral Bonding Jumper

---

 

AWG or kcmil

1/0

2

Minimum Conductor Size

 

 

(each)

(2)

(2)

Number (See Note 7)

 

 

 

 

 

NOTE: Callout letters A, B, C, and D map to Drawing 164201604 ---4, sheets 1 of 6,

2 of 6, 4 of 6, 5 of 6, and 6 of 6.

 

 

 

C A U T I O N

DELTA SOURCES (TN-S) - The Powerware 9390 UPS system can be operated only from a delta supply source that is fully floating and if the neutral-forming transformer kit (PN 103005400) is installed in the UPS. The UPS cannot be operated from a mid-point or end-point grounded delta supply source. With this type of supply source, there is no capability to provide an output neutral. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS.

8.The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the unit. Do not remove the debris shield until installation is complete. However, remove the shield before operating the UPS. Once the debris shield is removed, do not place objects on the ventilation grill.

9.Refer to Section I of this manual for installation instructions.

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

DRAWING NO:

164201604---5

 

SHEET:

3 of 15

 

 

 

 

 

REVISION:

B

 

DATE: 032406

 

A-14EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

Page 182
Image 182
Powerware 100160 kVA manual 6, 4 of 6, 5 of 6, and 6