Responding to System Events

NOTICES

Message

Horn

Phone

Relay

Log*

Indication

Automatic Shutdown Pending

1

No

No

A

Information Only

 

 

 

 

 

 

Automatic Shutdown Pending OK

OFF

No

No

A

Condition Cleared

 

 

 

 

 

 

Automatic Startup Pending

1

No

No

A

Information Only

 

 

 

 

 

 

Battery Current Limit

1

No

No

HA

Information Only

 

 

 

 

 

 

Battery Current Limit OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Battery Voltage High

1

1

No

HA

Information Only

 

 

 

 

 

 

Battery Voltage High OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Battery Voltage Low

1

No

No

HA

Information Only

 

 

 

 

 

 

Battery Voltage Low OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Bypass AC Over Voltage

1

No

No

HA

Information Only

 

 

 

 

 

 

Bypass AC Over Voltage OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Bypass AC Under Voltage

1

No

No

HA

Information Only

 

 

 

 

 

 

Bypass AC Under Voltage OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Bypass Phase Rotation

1

No

No

HA

Information Only

 

 

 

 

 

 

Bypass Phase Rotation OK

Off

No

No

A

Condition Cleared

 

 

 

 

 

 

Bypass Source Out of Tolerance

1

No

No

HA

Investigate UPS

 

 

 

 

 

 

Bypass Source Out of Tolerance OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Bypass Under or Over Frequency

1

No

No

HA

Information Only

 

 

 

 

 

 

Bypass Under or Over Frequency OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Charger Off Command

1

No

No

HA

Information Only

 

 

 

 

 

 

Charger On Command

1

No

No

HA

Information Only

 

 

 

 

 

 

Charger Over Voltage or Current

1

No

No

HA

Information Only

 

 

 

 

 

 

Charger Tripped

1

No

No

HA

Information Only

 

 

 

 

 

 

Charger Tripped OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Check Battery

1

No

No

HA

Information Only

 

 

 

 

 

 

Check Battery OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Check Modem

1

No

No

HA

Information Only

 

 

 

 

 

 

Check Modem OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

DC Link Over Voltage

1

1

No

HA

Information Only

 

 

 

 

 

 

DC Link Over Voltage OK

Off

No

No

A

Condition Cleared

 

 

 

 

 

 

DC Link Under Voltage

1

No

No

HA

Information Only

 

 

 

 

 

 

DC Link Under Voltage OK

Off

No

No

HA

Condition Cleared

 

 

 

 

 

 

Emergency Transfer To Bypass

1

No

No

HA

Information Only

 

 

 

 

 

 

Emergency Transfer To Bypass OK

Off

No

No

A

Condition Cleared

*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and A = Active log only.

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

12-5

Page 149
Image 149