Installation Information

1.Use Class 1 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be rated at 24V, 1A minimum.

2.Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30 to 600V.

3.When installing external interface wiring (for example, building alarm, relay output, battery breaker trip, and X-Slot) to the UPS interface terminals, conduit must be installed between each device and the UPS cabinet. Install the interface wiring in separate conduit from the power wiring.

4.When installing internal interface wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay.

5.All building alarm inputs or remote features require an isolated normally-open contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. All control wiring and relay and switch contacts are customer-supplied. Use twisted-pair wires for each alarm input and common.

6.The building alarms can be programmed to display the alarm functional name.

7.See Table R through Table X and Chapters 3, 5, and 6 for customer interface wiring.

8.LAN and telephone drops for use with X-Slot connectivity cards must be provided by facility planners or the customer.

 

 

Table R. TB1 and TB2 Interface Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal TB1

Name

 

 

Description

 

 

 

 

 

 

 

1

Remote EPO NC

Normally-closed dry contacts used to activate EPO

 

 

 

 

 

2

Remote EPO Common

of UPS from a remote switch

 

 

 

 

 

 

 

3

Remote EPO NO

Normally-open dry contacts used to activate EPO of

 

 

 

 

 

4

Remote EPO Common

UPS from a remote switch

 

 

 

 

 

 

 

5

Battery Breaker Aux

Contacts used to indicate whether UPS battery

 

 

 

 

 

 

Battery Breaker Aux

 

 

 

 

 

6

breaker or disconnect is open or closed.

 

 

 

 

Return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Battery UVR (+)

Contacts used to open battery breaker or

 

 

 

 

 

8

Battery UVR (---)

disconnect.

 

 

 

 

 

 

 

 

 

9

Building Alarm 1

Programmable UPS alarm. Activated by a remote

 

 

 

 

 

10

Building Alarm 1 Return

dry contact closure.

 

 

 

 

 

 

 

Terminal TB2

Name

 

 

Description

 

 

 

 

 

 

 

1

Building Alarm 2

Programmable UPS alarm. Activated by a remote

 

 

 

 

 

 

 

 

dry contact closure. Also used for backup control

 

 

 

 

 

2

Building Alarm 2 Return

 

 

 

 

(pull chain) for parallel operation.

 

 

 

 

 

 

 

3

On Bypass Return

Normally-open contact closes when UPS is on

 

 

 

 

 

 

 

 

bypass. Also used for backup control (pull chain)

 

 

 

 

 

4

On Bypass NO

 

 

 

 

for parallel operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Alarm Relay NC

General purpose normally-closed relay contact.

 

 

 

 

 

6

Alarm Relay Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Alarm Relay NO

General purpose normally-open relay contact.

 

 

 

 

 

8

Alarm Relay Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

On Inverter NC

Normally-closed contact opens when output

 

 

 

 

 

10

On Inverter Return

contactor closes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: INTERFACE WIRING INSTALLATION

 

 

 

 

 

 

 

 

 

NOTES AND TERMINAL LOCATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201604---8

 

 

SHEET: 1 of 13

 

 

 

 

 

 

 

REVISION:

B

 

DATE:

032406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S

164201604 Rev B powerware.com

A-33

Page 201
Image 201
Powerware 100160 kVA manual Description Interface Wiring Installation