UPS Operating Instructions

C A U T I O N

Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared.

3.To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph 10.2.1 or 10.2.2.

10.2.9Using the Parallel System Remote Emergency Power-off Switch

A parallel system emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this switch to control the UPM outputs. The REPO switch de-energizes the critical load and powers down the UPMs immediately, without asking for verification.

The UPMs, including Bypass, remain off until restarted.

C A U T I O N

All power to the critical load is lost when the REPO switch is activated in the following step. You should use this feature only when you want to de-energize the critical load.

NOTE The following instructions are for the Powerware-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.

To use the REPO switch:

1.Press the REPO pushbutton switch.

The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the power module is turned off immediately, without asking for verification.

C A U T I O N

Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared.

2.To restart the UPMs after using the REPO pushbutton, reset the REPO switch and then follow the procedure in paragraph 10.2.1 or 10.2.2.

10-14EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com