Using Features and Options

11.5 Supervisory Contact Module II

An optional SCM II establishes an interface between the UPS system and the customer’s monitor. This interface allows the customer to monitor operational status of the UPS system equipment. The SCM II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 11-3 shows the SCM II.

Figure 11-3. Supervisory Contact Module II

The SCM II provides signals for the indications shown in Table 11-3.

Table 11-3. SCM II Status Indicators and Connections

Indication

TB-2 Connections

SYSTEM NORMAL

TB2-1 through TB2-3

 

 

NO REDUNDANCY

TB2-4 through TB2-6

 

 

ON GENERATOR

TB2-7 through TB2-9

 

 

BYPASS NOT AVAILABLE

TB2-10 through TB2-12

 

 

ON BATTERY

TB2-13 through TB2-15

 

 

UPS ALARM

TB2-16 through TB2-18

 

 

ON BYPASS

TB2-19 through TB2-21

 

 

SHUTDOWN IMMINENT

TB2-22 through TB2-24

 

 