4.Pull out the battery drawer.
5.Move the gravity latch to the down position. Lock the telescopic slide into the locked out position.
6.Install the batteries in the drawer as follows, referring to Figure 36 for extended batteries and Figure 37 for extended batteries:
a.Place the batteries in the drawer in the configuration shown.
b.Wire the batteries in series as shown.
c.Find the wiring harness coiled up on the floor of the battery back up drawer and plug the Anderson connectors together as shown.
7.Move the gravity latch up, push the battery drawer in, and move the gravity latch down.
8.Reconnect the battery disconnect switch (DISC) on the LVD unit. For location, refer to Figure 19 on Page 24. The LVD LED on the low voltage disconnect unit should will turn off when the batteries are reconnected.
GRAVITY
BATTERYLATCH
DRAWER
Figure 35. Open Battery Drawer
Page 52
© 2007, ADC Telecommunications, Inc.