ADCP-75-210 • Issue 1 • March 2007

7.Using cable 1001475P001, connect the PA CTL1/3 connector on the RUC module to either of the following as appropriate:

CNTL port on PAA1 if RUC module is in slot A2

CNTL port on PAA3 if RUC module is in slot A5

8.Using cable 1001475P001, connect the CTL 2/4 connector on the RUC module to either of the following as appropriate:

CNTL port on PAA2 if RUC module is in slot A2

CNTL port on PAA4 if RUC module is in slot A5

4.2Installing cPCI Chassis Air Baffles

The air baffles for the RAN chassis are used in all empty chassis slots. This is done to maintain airflow around the chassis modules.

Use the following procedure to install air baffles:

1.Identify designated RAN Chassis cPCI slot for the cPCI air baffle.

2.Insert air baffle into designated slot on chassis and tighten screws.

4.3Installing a Rectifier Module

To install a rectifier module, use the following procedure (Figure 47):

Note: For a description of the rectifier including function, controls, and indicators, refer to Section 1.8 on Page 23. For a RAN chassis interconnection diagram, refer to Figure 40 on Page 58.

1.Connect cables following Section 22 on Page 66.

2.Slide the rectifier into the rectifier compartment.

3.Turn the gravity latch down to lock the rectifier in place.

Table 22. Rectifier Ports and Connections

RECTIFIER PORT

CONNECTS TO

USING CABLE

COMMENTS

L1, L2, L3

EMI Line Filter

1001473P001

Connect black wire to F-L1 (on EMI Line Filter); connect

 

F-L1, F-L2

 

brown wire to FL-2

 

 

 

 

RECT GND

GND Stud

1001473P001

Connect to cabinet ground stud

 

 

 

 

+BAT, -BAT

Anderson con-

1001477P001

Connect to Anderson connector in battery compartment;

 

nector

 

connect black wire to 0V (+BAT) and blue wire to -BAT

 

 

 

 

OV OUT,

temp sensor,

1001477P001

Place temperature sensor in battery compartment; connect

-OV OUT

circuit break-

1001469P001

1001477P001 black wire to OV OUT and blue wire to -

 

ers REC+ and

1001470P001

OV OUT; connect 1001469P001 from rectifier OV OUT

 

REC-

 

to circuit breaker POS; connect 1001470P001 from recti-

 

 

 

fier -OV OUT to circuit breaker NEG

 

 

 

 

Page 66