© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Exhaust Requirements
27
70420801 (EN)
Individual Venting
For maximum efficiency and performance, it is
preferred to exhaust tumble dryer(s) individually to
the outdoors.
IMPORTANT: At no point may the cross sectional
area of installed venting be less than the cross
sectional area of the exhaust outlet of the tumble
dryer.
The exhaust duct must be designed so the static back
pressure measured 12 inches (305 mm) from the
exhaust outlet does not exceed the maximum
allowable pressure specified on the installation sticker
on the rear of the tumble dryer.
NOTE: Static back pressure must be measured
with the tumble dryer running.
The maximum allowable length of vent ing of the same
diameter as the exhaust thimble is 14 feet (4.3meters)
and two 90° elbows or equivalent. If the equivalent
length of a duct required for an installation exceeds the
maximum allowable equivalent length, the diameter of
a round duct must be increased by 10% for each
additional 20 feet (6.1 meters). Cross sect ion area of a
rectangular duct must be increased by 20% for each
additional 20 feet (6.1 meters). Refer to Table 4 to
determine equivalent venting:
With the tumble dryer in operation, airflow at any
point in the duct should be at least 1200 feet pe r
minute (366 meters per minute) to ensure that lint
remains airborne. If 1200feet per minute (366 meters
per minute) cannot be maintained, schedule monthly
inspections and cleaning of the ductwork.
NOTE: The maximum length of a flexible metal
duct must not exceed 7.87 ft. (2.4 m) as required to
meet UL2158, claus 7.3.2A.
Manifold Venting
While it is preferable to exhaust tumble dryers
individually to the outdoors, a main col lector duct may
be used if it is sized according to Figure 8. This
illustration indicates minimum diameters, and should
be increased if collector length exceeds 20 feet (6.1
meters). Manifold duct may be rectangular in cross
section, as long as area is not reduced. Provisions
should be made for lint removal and cleaning of duct.
Manifold duct must be tapered, as shown in Figure6.
Individual tumble dryer ducts must enter manifold
duct at a 45° angle in the direction if airflow.
NOTE: Never connect a tumble dryer duct at a 90°
angle to a collector duct. Refer to Figure6. Doing
so will cause excessive back pressure, resulting in
poor performance. Never connect two tumble
dryer exhaust ducts directly across from each other
at the point of entry to manifold duct.
Figure 6
Exhaust system must be designed so sta tic back
pressure measured 12 inches (305 mm) from exhaust
thimble does not exceed maximum allowable pressure
specified on installation sticker on rear of tumble
dryer. This must be measured with all tumble dryers
running that are vented into collector.
With the tumble dryer in operation, airflow at any
point in the duct should be at least 1200 feet per
minute (366meters per minute) to ensure that lint
remains airborne. If 1200 feet per minute (366 meters
per minute) cannot be maintained, schedule monthly
inspections and cleaning of the ductwork.
Duct Diameter Equivalent Length
of Rigid Straight Duct
10 in. (254 mm)
12 in. (305 mm)
14 in. (356 mm)
16 in. (406 mm)
18 in. (457 mm)
One 90° elbow = 11.6 ft. (3.5 m)
One 90° elbow = 14 ft. (4.3 m)
One 90° elbow = 16 ft. (4.9 m)
One 90° elbow = 18.7 ft. (5.7 m)
One 90° elbow = 21 ft. (6.4 m)
Equivalent Length (ft.) = 1.17 x Duct Diameter (in.)
Table 4
Example: A 12 inch (305 mm) diameter duct’s
equivalent length of 14 feet (4.3 meters) of duct and two
90° elbows is:
Equivalent Length: = 14 ft. (4.3 m) + (2) 90° elbows
= 14 ft. (4.3 m) + 14 ft. (4.3 m)
+ 14 ft. (4.3 m)
= 42 ft. (12.8 m)
T438I