© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Electrical Requirements
70420801 (EN)
42
Electrical Requirements
Refer to Tabl e 9.
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: 3 Phase Only– Each tumble dryer must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
For 120 Pound Gas and Steam Tumble Dryer Models
Serial Plate Rating Terminal Block
Connections Required
Rated
Current*
(amps)
Breaker
Rating
Recommended Wire
Size AWG (mm²)
200-208V/60Hz/3ph L1,L2,L3 and ground 7.7 15A - 3 pole 14 (2.08)
230V/50Hz/3ph L1,L2,L3 and ground 7.3 15A - 3 pole 14 (2.08)
240V/60Hz/3ph L1,L2,L3 and ground 7.3 15A - 3 pole 14 (2.08)
380V/50 or 60Hz/3ph L1,L2,L3 and ground 4.1 10A - 3 pole 14 (2.08)
400-415V/50Hz/3ph L1,L2,L3 and ground 3.8 10A - 3 pole 14 (2.08)
440V/60Hz/3ph L1,L2,L3 and ground 3.8 10A - 3 pole 14 (2.08)
460-480V/60Hz/3ph L1,L2,L3 and ground 3.9 10A - 3 pole 14 (2.08)
* Current ratings vary slightly depending on model; refer to serial plate.
For 120 Pound Electric Tumble Dryer Models
Serial Plate Rating Terminal Block
Connections Required
Rated
Current*
(amps)
Breaker
Rating
Recommended Wire
Size AWG (mm²)
240V/60Hz/3ph L1,L2,L3 and ground 152 175A - 3 pole 3/0 (85)
380V/50 or 60Hz/3ph L1,L2,L3 and ground 94.5 125A - 3 pole 1 (42.4)
400-415V/50Hz/3ph L1,L2,L3 and ground 87 125A - 3 pole 1 (42.4)
480V/60Hz/3ph L1,L2,L3 and ground 76.1 100A - 3 pole 3 (26.2)
* Current ratings vary slightly depending on model; refer to serial plate.
For 170 Pound Tumble Dryer Models
Serial Plate Rating Terminal Block
Connections Required
Rated
Current*
(amps)
Breaker
Rating
Recommended Wire
Size AWG (mm²)
200-208V/60Hz/3ph L1,L2,L3 and ground 13.5 20A - 3 pole 12 (3.31)
240V/60Hz/3ph L1,L2,L3 and ground 13.5 20A - 3 pole 12 (3.31)
380V/50 or 60Hz/3ph L1,L2,L3 and ground 6.9 15A - 3 pole 14 (2.08)
400-415V/50Hz/3ph L1,L2,L3 and ground 6.9 15A - 3 pole 14 (2.08)
440V/60Hz/3ph L1,L2,L3 and ground 6.4 15A - 3 pole 14 (2.08)
460-480V/60Hz/3ph L1,L2,L3 and ground 6.7 15A - 3 pole 14 (2.08)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 9