Displayed Alarm Message | Action Required |
|
|
Group Configuration Invalid | • Check that the # Systems setting (Path: Main > Setup > Group > Group |
| Config) agrees with the actual number of Systems connected to the Group. |
| Adjust this setting to match the number of connected Systems. |
|
|
Group Configuration Conflict | • Verify the Group configuration settings (Path: Main > Setup > Group) are |
| correct. The Group detected that one or more Systems in the Group have |
| different Group configuration settings and changed the settings of that |
| System. |
|
|
Group Fatal Fire Shutdown | • Check the Systems in this Group for fire alarms. The Group Fatal Fire |
| Shutdown occurs only when the Group Fire Alarm configuration setting |
| (Path: Main > Setup > Group Config > Grp Fire Alrm) is On. While the |
| fire alarm is active, the Group will remain shut down. |
|
|
Group Fatal Smoke Shutdown | • Check the Systems in this Group for smoke alarms. The Group Fatal Smoke |
| Shutdown occurs only when the Group Smoke Alarm configuration setting |
| (Path: Main > Setup > Group Config > Grp Smoke Alrm) is On. While |
| the smoke alarm is active, the Group will remain shut down. |
|
|
Head Pressure High | • Confirm that the |
| setpoints are correct. |
| • For water/glycol configuration, confirm that the condenser loop pumps are |
| operating properly. |
| • Ensure that the |
| • Verify that all isolation valves to the condenser loop or interconnecting |
| piping are open. |
| • For water/glycol cooled configuration, confirm that all air has been purged |
| from the condenser loop. |
| • For water/glycol cooled configuration, confirm that the |
| concentration is 40% glycol to 60% water. |
| • Verify (water/glycol) cooled configuration, confirm the indoor Module and |
| outside heat exchanger that interconnects between the wiring. |
| • Verify (water/glycol) correct operation of the condenser fluid valve actuator. |
| • Confirm proper refrigerant charge in the Module. |
| • Ensure that the Module is set to the proper heat of rejection method on the |
| display interface (Path: Main Menu > Setup > System # > System Config |
| > System Options). |
| • Verify (water/glycol) cooled configuration, that the strainers are clear and |
| open. |
| • Confirm the proper operation and trip point of the high head pressure switch. |
| • Evaluate field piping for proper line sizes and proper installation. |
| • Verify that the Economizer isolator valve is open (if installed). |
|
|
Heater Requires Maintenance | • Verify the operation of the heater and perform preventive maintenance. |
| • Reset the maintenance alarm for the heater at the display interface. |
|
|
Humidifier Current High | • Verify that the proper voltage is being applied to the humidifier cylinder. |
| • Confirm that there are secure and proper line voltage connections to the |
| humidifier cylinder. |
| • Ensure that the humidifier water supply has not been conditioned. |
| Conditioning can increase the water conductivity. |
| • Check the electrodes in the humidifier cylinder for mineral buildup that |
| bridges the electrodes. |
| • Check the fill valve for debris which may prevent the valve from closing. |
|
|
56 | NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting |