Measure the refrigerant pressures.

Functional tests

Measure the refrigerant pressures.

Head Pressure

Suction Pressure

Compressor on

Compressors on

Check the operation of the thermal expansion valve. Verify superheat and sub-cooling of the System in full cool mode:

Superheat ________________

Sub-cooling ______________

Check the operation of the head pressure switch:

Cut-out PSI (kPa)_____________

Verify the operation of the water/glycol regulating valves.

Check the operation of the smoke, fire, and water detected alarms (if applicable).

Confirm the operation of the fluid cooler or air cooled condenser and the flooded head pressure controls, if used.

Confirm the operation of the Redundant Group and change over capabilities.