Displayed Alarm Message | Action Required |
|
|
Supply Humidity High | • Verify that the suction pressure is not below 58 psig (400 kPa). |
| • Ensure that the alarm delay is not set too low. The delay should be long |
| enough to allow the Module to control the humitity after |
| • Ensure the alarm threshold for the humidity of the supply air is set above the |
| humidify and dehumidify setpoints. |
| • Verify that there is proper airflow through the Module. (Check the pressure |
| drop across the evaporator coil.) |
| • Check the capacity output of the humidifier and reduce it if required. |
| • Ensure that there is a proper vapor barrier within the conditioned space. |
| • Verify that the Module is configured and equipped for the dehumidify mode. |
| • Ensure the dehumidify mode is enabled. |
| • Ensure the dehumidify mode is not disabled because of an active custome |
| input mapped to a nonessential lockout. |
|
|
Supply Humidity Low | • Ensure the alarm delay is not set too low. The delay should be long enough to |
| allow the Module to control the humidity after |
| • Ensure the alarm threshold for the humidity of the supply air is set below the |
| humidify and dehumidify setpoints. |
| • Check the capacity output of the humidifier and increase it if required. |
| • Ensure there is a proper vapor barrier within the conditioned space. |
| • Verify the Module is configured and equipped for the humidify mode. |
| • Ensure the jumidify mode is enabled. |
| • Ensure the humidify mode is not disabled because of an active customer |
| input mapped to a nonessential lockout. |
|
|
Supply Sensor Fail | • Verify that there is a proper CAN connection between the sensors and the |
| user interface box. |
| • Check the connections of the 25 pin serial communication cable from the |
| main controller board to the customer interface box. |
| • Replace the sensor assembly. |
|
|
Supply Temperature High | • Ensure that the alarm delay is not set too low. The delay should be long |
| enough to allow the Module to control the temperature after |
| • Verify that the supply air temperature alarm threshold is set above the cool |
| and reheat setpoints. |
| • Verify that there is proper airflow through the Module (check the pressure |
| drop across the evaporator coil). |
| • Ensure that the cool mode is enabled. |
| • Ensure that the cool mode is not disabled because of an active customer input |
| mapped to nonessential lockout. |
|
|
Supply Temperature Low | • Ensure that the alarm delay is not set too low. The delay should be long |
| enough to allow the Module to control the temperature after |
| • Verify that the Module is configured and equipped for the reheat mode. |
| • Ensure that the supply air temperature alarm threshold is set below the reheat |
| and cool setpoints. |
| • Ensure that the reheat mode is enabled. |
| • Ensure that the reheat mode is not disabled because of an active customer |
| input mapped to nonessential lockout. |
| • Verify that there is proper airflow through the Module (check the pressure |
| drop across the evaporator coil). |
|
|
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting | 59 |