American Power Conversion FM, DX Displayed Alarm Message, Action Required, Supply Humidity High

Models: DX FM

1 96
Download 96 pages 14.45 Kb
Page 69
Image 69

Displayed Alarm Message

Action Required

 

 

Supply Humidity High

• Verify that the suction pressure is not below 58 psig (400 kPa).

 

• Ensure that the alarm delay is not set too low. The delay should be long

 

enough to allow the Module to control the humitity after start-up.

 

• Ensure the alarm threshold for the humidity of the supply air is set above the

 

humidify and dehumidify setpoints.

 

• Verify that there is proper airflow through the Module. (Check the pressure

 

drop across the evaporator coil.)

 

• Check the capacity output of the humidifier and reduce it if required.

 

• Ensure that there is a proper vapor barrier within the conditioned space.

 

• Verify that the Module is configured and equipped for the dehumidify mode.

 

• Ensure the dehumidify mode is enabled.

 

• Ensure the dehumidify mode is not disabled because of an active custome

 

input mapped to a nonessential lockout.

 

 

Supply Humidity Low

• Ensure the alarm delay is not set too low. The delay should be long enough to

 

allow the Module to control the humidity after start-up.

 

• Ensure the alarm threshold for the humidity of the supply air is set below the

 

humidify and dehumidify setpoints.

 

• Check the capacity output of the humidifier and increase it if required.

 

• Ensure there is a proper vapor barrier within the conditioned space.

 

• Verify the Module is configured and equipped for the humidify mode.

 

• Ensure the jumidify mode is enabled.

 

• Ensure the humidify mode is not disabled because of an active customer

 

input mapped to a nonessential lockout.

 

 

Supply Sensor Fail

• Verify that there is a proper CAN connection between the sensors and the

 

user interface box.

 

• Check the connections of the 25 pin serial communication cable from the

 

main controller board to the customer interface box.

 

• Replace the sensor assembly.

 

 

Supply Temperature High

• Ensure that the alarm delay is not set too low. The delay should be long

 

enough to allow the Module to control the temperature after start-up.

 

• Verify that the supply air temperature alarm threshold is set above the cool

 

and reheat setpoints.

 

• Verify that there is proper airflow through the Module (check the pressure

 

drop across the evaporator coil).

 

• Ensure that the cool mode is enabled.

 

• Ensure that the cool mode is not disabled because of an active customer input

 

mapped to nonessential lockout.

 

 

Supply Temperature Low

• Ensure that the alarm delay is not set too low. The delay should be long

 

enough to allow the Module to control the temperature after start-up.

 

• Verify that the Module is configured and equipped for the reheat mode.

 

• Ensure that the supply air temperature alarm threshold is set below the reheat

 

and cool setpoints.

 

• Ensure that the reheat mode is enabled.

 

• Ensure that the reheat mode is not disabled because of an active customer

 

input mapped to nonessential lockout.

 

• Verify that there is proper airflow through the Module (check the pressure

 

drop across the evaporator coil).

 

 

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting

59

Page 69
Image 69
American Power Conversion FM, DX manual Displayed Alarm Message, Action Required, Supply Humidity High