Displayed Alarm Message

Action Required

 

 

Humidifier Cylinder Depleted

• Replace the disposable cylinder.

 

• Clean the reusable humidifier cylinder (optional).

 

 

Humidifier Cylinder Full When

• Check the humidifier fill and drain valves for clogging.

Off

• Check the operation of the humidifier drain solenoid.

 

 

Humidifier Drain Malfunction

• Ensure that the drain is free of any debris.

 

• Verify the operation of the drain solenoid valve.

 

 

Humidifier Excessive Foam

• Verify that the humidifier water supply is not using conditioned water and

 

that the water does not contain contaminates.

 

• Check the humidifier water supply hose for dirt and contaminates.

 

• Drain the humidifier canister and refill with fresh water.

 

 

Humidifier Excessive Output

• Reduce the humidifier sensitivity setting on the display interface (Path:

Reduction

Main > Setup > System # > System Config > Humid. Sensitivity) if

 

necessary.

 

 

Humidifier Fail

• Check the event log for other humidifier alarms.

 

 

Humidifier Fault Tolerance

• Humidifier has experienced three faults within 30 minutes.

Exceeded

• Reset the humidifier from the display interface (Path: Main > Setup >

 

Module > [Module Alarm Occurred in] > Module Control > Reset

 

Humidifier).

 

• Check the alarm status and event log for humidifier alarms and perform

 

required actions.

 

 

Humidifier Internal Memory

• Check the controller connections to the humidifier for electrical discharge.

Error

 

 

 

Humidifier No Power

• Verify that the humidifier circuit breaker has not been tripped.

 

• Confirm that the line voltage connections to the cylinder are secure and

 

correct.

 

 

Humidifier Requires

• Verify the operation of the humidifier and perform preventive maintenance.

Maintenance

• Reset the maintenance alarm for the humidifier at the display interface.

 

 

Humidifier Water Conductivity

• Verify that the proper voltage is being applied to the humidifier cylinder.

High

• Confirm that the line voltage connections to the cylinder are secure and

 

correct.

 

• Ensure that the water supply to the humidifier has not been conditioned.

 

Conditioned water can increase water conductivity.

 

 

Humidifier Water Level Low

• Verify that the humidifier water supply is open and flowing to the humidifier

 

water connection.

 

• Confirm that the inlet water strainer on the humidifier fill solenoid is clear

 

and free of debris.

 

• Ensure that the water pressure is at least 206 kPa (30 psig).

 

• Verify the operation of the fill solenoid valve.

 

• Check the drain valve for debris which may prevent the valve from closing.

 

• Check the steam supply hose for kinks or sags that may cause back pressure.

 

 

Module # Failed

• Check the event log for other alarms for this Module.

 

 

Module Powered Up

• The Module has successfully started.

 

 

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting

57

Page 67
Image 67
American Power Conversion FM, DX manual Module Module Alarm Occurred in Module Control Reset

DX, FM specifications

The American Power Conversion (APC) DX,FM series represents a cutting-edge solution designed for critical power management and uninterruptible power supply (UPS) applications. Aimed at businesses and data centers that require robust power protection, this series balances high-performance capabilities with advanced technology features.

One of the key distinguishing features of the DX,FM series is its modular design. This allows users to scale their UPS system according to their needs, making it suitable for a variety of environments. Whether you're managing a small server room or a large data center, the modular architecture ensures that you can add or remove capacity with ease. This flexibility not only optimizes initial investments but also supports future growth seamlessly.

The series employs advanced battery technology, which extends battery life and enhances overall performance. With intelligent battery management systems, the DX,FM ensures that battery health is monitored in real-time, preventing premature failures and unnecessary replacements. This leads to reduced maintenance costs and maximizes uptime.

Additionally, the DX,FM series features innovative cooling solutions that enhance performance in high-density situations. Efficient thermal management reduces the risk of overheating, keeping valuable equipment operating optimally. This is particularly crucial in data centers where heat generated by servers can create potential disruptions.

Another significant characteristic of the DX,FM series is its sophisticated monitoring and management capabilities. Integrated with state-of-the-art software, users can gain remote access to their UPS units, enabling real-time tracking of performance metrics. This remote monitoring capability allows administrators to proactively manage power usage and ensure that systems are operating within safe parameters.

Furthermore, the DX,FM series is designed with a high level of redundancy. This built-in reliability feature ensures that if one unit fails, others can seamlessly take over, maintaining power supply continuity. This is critical for mission-critical environments where power outages could result in substantial financial losses or data loss.

In summary, the American Power Conversion DX,FM series incorporates modularity, advanced battery technology, effective cooling solutions, and sophisticated monitoring features to deliver an ideal power management solution for various organizations. Its design prioritizes flexibility, reliability, and efficiency, making it an essential investment for any business looking to safeguard its operations against power disruptions.