The following graphic is an example of a
Cool Deadband Compressor Allocation
Two-Module System
Compressor | Compressor | Compressor | Compressor |
# 1 | # 2 | # 3 | # 4 |
21° | 21.6° | 22.2° | 22.7° | 23.3° |
(70°) | (71°) | (72°) | (73°) | (74°) |
Return air temperature
na0437a
Caution: If the deadband setting is too narrow, it will cause the System to engage the compressors in response to a small temperature change. Since the compressors must run for a minimum period to avoid damage, this could
Caution: If the deadband setting is too wide, the System will not engage all of its cooling capacity until the return air temperature is significantly above the setpoint.