Modes

Modes

Path: Main > Control Environment > Modes

Cool:

Enabled

 

Reheat:

Disabled

 

Dehumid:

Enabled

na0430a

Humidify:

Enabled

 

 

 

 

Enable and disable the modes of operation. The four modes are:

Cool

Reheat

Dehumidify

Humidify

Modes can only be enabled or disabled using the service password.

Essential functions

Path: Main > Control Environment > Essential Functions

Designate each mode as either essential or nonessential. The modes marked as nonessential are disabled when an alarm or event occurs that requires all nonessential operations to be stopped (nonessential lockout).

Cool: Essential

Reheat: Nonessent.

Dehumid: Nonessent.

Humidify:Nonessent.

na0431a

See “Input contacts” on page 25 for a table with descriptions of how you can set up nonessential lockout events that occur when an input contact becomes active.

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting