American Power Conversion FM, DX Problem, Possible Cause, Corrective Action, Compressor noisy

Models: DX FM

1 96
Download 96 pages 14.45 Kb
Page 87
Image 87

Problem

Possible Cause

Corrective Action

Compressor noisy

• Compressor or compressors may

• Verify the pressure differential across the

 

be rotating in the wrong direction

suction and discharge for each compressor. If

 

 

no differential is present, verify the correct

 

 

phasing to each compressor.

 

• Liquid slugging

• Check for low evaporator superheat.

 

 

• Check operation of crankcase heaters.

 

 

• Verify liquid line solenoid valves close tightly

 

 

during the off cycle. Check for obstructions

 

 

which may prevent the valve from closing.

 

• High head pressure

• Check operating head pressure.

 

 

 

Controls erratic or

• Control transformer problem

• Check control transformers for proper input

inoperative

 

voltage.

 

 

• Check control transformer secondary voltage.

 

 

Output should be within + or - 10% of rated

 

 

output.

 

• Loose or broken wiring

• Check wiring for loose or broken connections.

 

• Module configured incorrectly

• Set module configuration according to

 

 

nameplate and options selected.

 

• System is in alarm

• Check front panel display for active system

 

 

alarm.

 

 

 

Evaporator coil ices

• Dirty or blocked evaporator coil

• Clean evaporator coil.

 

• Dirty or blocked air filters

• Check filters and replace as needed.

 

• Low airflow

• Check for correct airflow setting.

 

• Low evaporator superheat

• Check superhear and adjust to 10-15°F.

 

• Low return air temperature

• Verify the return air temperature is not below

 

 

20ºC (68°F).

 

• Low refrigerant charge

• Check for short cycling of cold supply air.

 

• Check subcooling and ensure it is at least

 

 

10-15°F. Repair leak and recharge system.

Head pressure too

• Air cooled condenser malfunction

• Check and clean the condenser coil. Check

high

 

condenser fan operation and settings.

 

• Condenser water regulating valve

• Check water regulating valve, actuator, and

 

malfunction

linkage for proper operation.

 

• Overcharge of refrigerant

• Remove excess refrigerant from system.

 

Non-condensable in system

• Recover refrigerant charge, evacuate system

 

 

and recharge.

 

• Fluid cooler malfunction

• Check and clean the fluid cooler coil. Check

 

 

fluid cooler fan operation.

 

• Fluid pump malfunction

• Check pump operation.

 

• Low fluid flow

• For water cooled systems, check the condenser

 

 

water flow rate and water supply temperature.

 

 

Check pressure drop across the heat

 

 

exchanger. Check and clean field installed

 

 

strainers.

 

 

• For glycol cooled systems, check the water

 

 

flow rate and water supply temperature. Check

 

 

pressure drop across the heat exchanger.

 

• Glycol concentration higher than

Check and clean field installed strainers.

 

40%

• Verify glycol concentration, reduce to

 

 

maximum 40%.

 

 

 

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting