American Power Conversion FM, DX Problem, Possible Cause, Corrective Action, Suction pressure too

Models: DX FM

1 96
Download 96 pages 14.45 Kb
Page 89
Image 89

Problem

Possible Cause

Corrective Action

Suction pressure too

• Dirty or blocked evaporator coil

• Clean evaporator coil.

low

• Dirty or blocked air filters

• Check filters and replace as needed.

 

• Low airflow

• Check for correct airflow setting.

 

• Low return air temperature

• Verify the return air temperature is not below

 

 

20ºC (68°F).

 

 

• Check for short cycling of cold supply air.

 

• Low refrigerant charge

• Check subcooling and ensure it is at least

 

• Liquid line filter drier is blocked

10-15°F. Repair leak and recharge system

 

• Check filter drier for excessive pressure drop.

 

• High evaporator superheat

• Check for proper superheat and TXV

 

 

operation.

 

 

 

System short of

• Low refrigerant charge

• Check subcooling and ensure it is at least

capacity

• Liquid line filter drier is blocked

10-15°F. Repair leak and recharge system.

 

• Check filter drier for excessive pressure drop.

 

• High evaporator superheat

• Check for proper superheat and TXV

 

• Insufficient air quantity across the

operation.

 

• Check for correct airflow and clean filters.

 

evaporator coil

 

 

• Excessive outside air infiltration

• Reduce outside air infiltration.

 

• Lack of proper room vapor barrier

• Install vapor barrier materials on floor, walls,

 

 

and ceiling as needed.

 

 

 

Temperature control

• Excessive outside air infiltration

• Reduce outside air infiltration.

not tight enough

• Lack of proper room vapor barrier

• Install vapor barrier materials on floor, walls,

 

 

and ceiling as needed.

 

• Cool/reheat setpoints not close

• Check cooling and reheat setpoints and

 

enough

deadbands.

 

• Reheat PID loop is not properly

• Tune the PID loop for accurate reheat

 

tuned

operation.

 

• Interstage delay is too large

• Reduce the interstage delay to allow quicker

 

 

response to temperature changes.

 

• Return air temperature does not

• Check for short cycling of cold supply air.

 

reflect actual room condition

• Check air distribution for deficiencies.

 

 

• Consider using remote sensor control.

 

 

Note: Be certain to purchase the correct

 

 

temperature and humidity probe. Check when

 

 

ordering that your equipment is compatible.

 

 

 

Water carryover

• Dirt or oil residue on evaporator

• Clean the evaporator coil.

 

coil

• Check for correct airflow and clean filters.

 

• Insufficient air quantity across the

 

evaporator coil

• Reduce airflow to specifications.

 

• Excessive airflow across the

 

evaporator coil

• Clean condensate pan and drain line.

 

• Blockage in condensate pan or

 

drain line

• Verify the return air temperature is not below

 

• Low return air temperature

 

 

20ºC (68ºF).

 

 

• Check for short cycling of cold supply air

 

• High return humidity

• Lower humidity setpoint.

 

 

• Check for short cycling of supply air

 

• Excessive outside air infiltration

• Reduce outside air infiltration.

 

• Lack of proper room vapor barrier

• Install vapor barrier materials on floor, walls,

 

 

and ceiling as needed.

 

 

 

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting

79