American Power Conversion FM, DX Displayed Alarm Message, Action Required, Env Temperature Low

Models: DX FM

1 96
Download 96 pages 14.45 Kb
Page 65
Image 65

Displayed Alarm Message

Action Required

 

 

Env Temperature Low

• Verify that no supply air is fed directly back into the return air.

 

• Ensure that the alarm delay is not set too low. The delay should be long

 

enough to allow the room temperature to stabilize after start-up.

 

• Verify that the temperature alarm threshold for the environmental (return or

 

remote) sensors is 7 - 10°F below the reheat setpoint.

 

• Verify that the Module is configured and equipped for the reheat mode.

 

• Ensure that the reheat mode is enabled and working properly.

 

• Ensure that the reheat mode is not disabled because of an active user-defined

 

input mapped to nonessential lockout.

 

 

Exp Module # 1

• Verify the System CAN connections in the user interface box are connected

Communication Lost

correctly and properly terminated.

 

• Check the CAN addresses assigned with the DIP switches on the controller

 

board on the electrical panel. NOTE: The controller must be restarted to

 

recognize an address change.

 

 

Exp Module # 2

• Verify the System CAN connections in the user interface box are connected

Communication Lost

correctly and properly terminated.

 

• Check the CAN addresses assigned with the DIP switches on the controller

 

board on the electrical panel.

 

 

Fire Detected

• Follow the appropriate facility emergency protocol. NOTE: The purpose of

 

the fire sensor is to warn you of possible equipment damage. It is NOT

 

intended to provide a fire alarm system to protect the facility and the lives of

 

its occupants.

 

• Confirm that the wiring connections are secured to the wiring harness.

 

• Verify the fire detector (firestat) is set to 125°F.

 

• Reset the firestat by pressing the reset button on the firestat.

 

• Replace the fire detector (firestat).

 

 

Fluid Coil No Coolant Flow

• Verify chilled water supply.

 

• Check the operation of the flow switch.

 

• Check the electrical connection to the flow switch.

 

• Verify that the Economizer automatic coolant isolation valve is open (if

 

equipped).

 

• Verify that the valve type setting is correct in the System Configuration

 

(Path: Main > Setup > System # > System Config > Valve Types).

 

 

Fluid Coil Actuator Fail

• Verify the proper connections between the actuator and the controller board.

 

• Confirm that the control voltage and signal voltage reach the actuator.

 

• Ensure that the proper Module Configuration is defined for this Module,

 

especially that the coil Configuration and the MultiCool/Economizer actuator

 

type are correct.

 

• Replace the fluid coil actuator.

 

 

Fluid Coil Coolant Temp High

• For Economizer Modules, check the operation of the outdoor heat exchanger.

 

• For MultiCool Modules, check the chilled water supply temperature.

 

• Verify that the fluid coil coolant temperature high threshold is not set below

 

the normal temperature of your chilled water supply.

 

 

Fluid Coil Coolant Temp Low

• For Economizer Modules, check the operation of the outdoor heat exchanger.

 

• For MultiCool Modules, check the chilled water supply temperature.

 

• Verify that the low threshold for the fluid coil coolant temperature is not

 

set above the normal temperature of your chilled water supply.

 

 

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting

55

Page 65
Image 65
American Power Conversion FM, DX manual Displayed Alarm Message, Action Required, Env Temperature Low