2-25

Battery Backup:

Transfer Ti me to Batt ery
during blackout 7 ms typical,
10ms maximum 7 ms typical,
10ms maximum N/A
Battery Type & Quantity Four 12V/9A hr
sealed,
lead-acid,
maintenance free
Four 12V/9A hr
sealed,
lead-acid,
maintenance free
Eight 12V/9A hr
sealed, lead-acid,
maintenance free
Typical Recharge Time to
90% capacity <8 hrs <8 hrs N/A
Battery Service User replaceable &
Hot-swappable User replaceable
& Hot-swappable Not User
Serviceable
Battery Life12 to 5 Years 2 to 5 Years 2 to 5 Years
Battery Runtime2 33 min. (half load)
& 12 min.
(full load)
20 min (half load)
& 7.5 min.
(full load)
N/A
Surge Protection:
Let-Through Voltage
Rating <50V <50V N/A
Data Line Protection Jacks RJ45 RJ45 N/A
Coaxial Cable 3 pair + splitter 3 pair N/A
Ethernet 8 wire,
10/100BaseT None N/A
Telephone/DSL 2 line, 4 wire with
splitter 1 line, 2 wire
protection N/A
DC Trigger Two 3.5mm
mini-jack plugs
(5 to 30V)
Two 3.5mm
mini-jack plugs
(5 to 30V)
N/A
Physical:
Unit Dimensions 17 x 5.25 x
18.55 in
43.2 x 13 x
47.1 cm
17 x 5.25 x
18.55 in
43.2 x 13 x
47.1 cm
17 x 3.5 x
18.55 in
43.2 x 8.9 x
47.1 cm
Unit Weight 62 lbs / 28 kgs 60 lbs / 27 kgs 65 lbs / 30 kgs
Warranty: 2 years including
battery 2 years including
battery 2 years
Note1: Depends on usage, environment and operating temperature.
Note2: Actual runtimes are determined based on load, charge level, battery health, and the