Positioning the Equipment

Service access

An area of 1143 mm (45 in) of clear floor space in front and

914.4 mm (36 in) in back of the equipment is required for service. All required maintenance can be performed from the front or back of the equipment.

na1565a

Dimensions are shown in mm (in).

Leveling

The leveling feet provide a stable base if the floor is uneven, but cannot compensate for a badly sloped surface.

Once the equipment is in its intended location, use a screwdriver to turn each leveling foot until it makes contact with the floor. Adjust each foot until the equipment is level and plumb.

You can remove the casters and leveling feet to allow the

na1572a

equipment to rest directly on the floor.

 