Electrical Connections

The following electrical connections are required in the field:

Feeds A and B

A-Link

Network Management Card

Temperature sensor

Communication (building management system)

See the electrical schematic (located on the lid of the electrical box) for all electrical connections.

Make all electrical connections in accordance with national and local codes.

See the InRow RC nameplate for voltage and current requirements.

A power disconnect is required to isolate each InRow RC for maintenance and service.

All low-voltage connections, including data and control connections, must be made with properly insulated wires. The low-voltage connections must have 300-V minimum insulation.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Turn off all power supplying this equipment before working on the equipment.

Use a voltmeter to ensure that power is turned off before making any electrical connections.

Failure to follow these instructions will result in death or serious injury.

Note: Single phase service is required. Electrical service must conform to national and local electrical codes. The InRow RC is grounded through the power cord.

22

InRow RC Installation

Page 28
Image 28
APC ACRC103, ACRC100 manual Electrical Connections