Condensate pump. The pump is factory-wired and piped internally to the lower condensate pan. The pump is capable of moving liquid a maximum of 15.2 m (50 ft), including a maximum lift of 4.9 m (16 ft). For example, if your lift is 3 m (10 ft), you have 12.2 m (40 ft) of usable run. The pump also uses an on-board condensate high level float switch, which is wired into the InRow RC alarm input for local and remote alarm capabilities.

na1575a

CAUTION

CONDENSATE DAMAGE

Do not exceed the lift or the run length of the drain system.

To prevent equipment damage from condensate, do not leave the condensate drain line coiled inside the equipment. Route the condensate drain line out the top or bottom of the equipment before operation.

Failure to follow these instructions can result in equipment damage.

Condensate pump drain connection.

Note: Sufficient PVC drain line is

supplied to route the drain to the Condensate drain line outside of the equipment. To route the drain line to a remote drain,

obtain additional hardware.

na2271a

18

InRow RC Installation

Page 24
Image 24
APC ACRC103, ACRC100 manual Condensate pump drain connection