APC BC300 Series manual Battery Specifications, Dimensions/Weight

Models: BC300 Series

1 38
Download 38 pages 11.26 Kb
Page 36
Image 36

Technical Specifications

7.2Battery Specifications

 

40kW

 

 

Nominal DC current - Amps

200

 

 

UL rating of terminal blocks - AWGa

14 - 2/0

Nominal DC voltage

216

 

 

Nominal number of cells

108

 

 

Factory-set float charge voltageb

246

Charger current limit - Ampsc

20

Inverter efficiency -% 100% load

91

75% load

91

50% load

89

25% load

86

 

 

a.Terminal block has two positive and two negative 8 mm (=5/16”) studs, hardware provided. Lug re- quired.

Conductor size may vary based on installation re- quirements. Size all conductors per applicable codes.

b.Adjust the float charge voltage setting according to the battery manufacturer’s recommendations. c.Programmable to lower level.

7.3Dimensions/Weight

BC300 Series UPS

40kW

 

 

Height

59.1 inches

 

 

Width

39.4 inches

 

 

Depth

31.7 inches

 

 

Weight

1798 lbs

 

 

990-1401

36

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

Page 36