Installation

3.3.6 Communication Interface Board (Option)

Use Class 1 wiring methods.

 

X002

 

X001

 

 

 

 

 

 

 

 

 

Communication

Interface Board

X005

X004

X003

X003 25 PIN SUB D MALE

X004 25 PIN SUB D MALE

X005 25 PIN SUB D FEMALE

Serial Port

RS232

Serial Port

0-20 mA current loop

Relay Contacts: 30VAC, 60 VDC

Maximum 0.5 A, minimum 0.05 mA

14

15 "UPS on" (shown with UPS off)

2

16

17 "Static bypass operation" (shown with static bypass operation off) 4

18

19 "Battery operation" (shown with battery operation off)

6

20

21 "Battery low warning" (shown with "battery low" warning off) 8

13 +

Remote UPS shut down input (3.5 - 25 VDC pulse for 1 second minimum)

25 –

 

Figure 11 Communication Interface Board

990-1401

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

19

Page 19
Image 19
APC BC300 Series manual Communication Interface Board Option